http://chineseinput.net/에서 pinyin(병음)방식으로 중국어를 변환할 수 있습니다.
변환된 중국어를 복사하여 사용하시면 됩니다.
장영근,김석현 대한설비공학회 2002 설비공학 논문집 Vol.14 No.5
Simulations were carried out to investigate the characteristics of $CO_2$ emissions for an electric powered air conditioning system. The $CO_2$ emissions were evaluated for various simulation parameters such as a power source distribution rate, power plant efficiency, power supply efficiency and system performance (COP). It was found that the $CO_2$ emissions were remarkably decreased by increasing the COP of the electric powered air conditioning system with storage tank. The $CO_2$emission per unit refrigeration capacity is 0.6 kg/RTh. And also, as the COP increase by 0.1, the $CO_2$ emissions decrease by 7.2%.
온수 추출과정 동안 축열조 내의 열성층 특성 및 온수 이용률에 관한 연구
장영근,박정원 대한설비공학회 2002 설비공학 논문집 Vol.14 No.6
Heat flow characteristics during hot water extraction process was studied experimentally. Data were taken at various outlet port type for the fixed inlet port type, inlet-outlet temperature differences and mass flow rates. In this study, the temperature distribution in a storage tank and an outlet temperature were measured to predict a degree of stratification in the storage tank, and a useful rate of hot water was analysed with respect to the variables dominating a extraction process. Experimental results show that the degree of stratification and useful rate of hot water are all high in a low flow rate in case of using modified distributor I (MDI) as the outlet port type.