고전압 전력기기 개발을 위한 기중 임펄스절연파괴특성에 관한 연구
강형구(Hyoungku Kang),김준연(Joon-Yeon Kim),석복렬(Bok-Yeol Seok),김동해(Dong-Hae Kim) 대한전기학회 2009 대한전기학회 학술대회 논문집 Vol.2009 No.7
To develop electrically reliable high voltage apparatuses, the experimental study on the electrical breakdown field strength is needed, as well as theoretical approach. In this paper, lightning impulse breakdown characteristics considering utilization factors are investigated for the establishment of insulation design criteria of an high voltage apparatus. The utilization factors are represented as the ratio of mean electric field to maximum electric field. Dielectric experiments are performed by using five kinds of sphere-plane electrode systems made of stainless steel. As a result, it is found that dielectric characteristics are affected by not only gap length but also utilization factor of electrode systems. The results are expected to be applicable to the design of high voltage apparatuses.
고압배전반의 전기적 안정성 향상을 위한 버스바의 배치기법에 따른 전자기 특성에 관한 연구
남석호,허정일,홍종기,강형구,Nam, Seokho,Heo, Jeong Il,Hong, Jonggi,Kang, Hyoungku 한국전기전자재료학회 2013 전기전자재료학회논문지 Vol.26 No.3
The rated voltage has been rising in order to minimize the losses in power transmission. The high voltage electric machines should be minimized due to the constraints of space. Therefore, the temperature of high voltage electric apparatuses easily exceeds the temperature limits. In this paper, it is investigated that how to minimize the internal temperature rising of a high voltage switchgear by adjusting the arrangement of bus bars. High voltage switchgears consist of a circuit breaker, a CT, a PT, a earthing switches, bus bars, and so on. It is very difficult to estimate the electromagnetic properties of a high voltage switchgear due to these various environments and structures. In this paper, analyses are focused on the electromagnetic characteristics of bus bars according to the arrangement method and the enclosures to simplify the electromagnetic characteristics of a switchgear. It is found that the characteristics of electric field intensity and electromagnetic losses in bus bars are influenced by the arrangement method of bus bars. However, it is confirmed that the electromagnetic characteristics of enclosures are not affected by the arrangement of bus bars. In this paper, the arrangement methods of bus bars to minimize the electric field intensity and electromagnetic losses are suggested. It is expected that the research results are helpful to design and develop an electrically reliable high voltage switchgear.