22.9[kV] 다중접지 배전계통에서 고장전류의 접지저항 영향 분석
정금영,최선규,심건보,김경철,Jung, Kum-Young,Choi, Sun-Kyu,Shim, Keon-Bo,Kim, Kyung-Chul 한국조명전기설비학회 2010 조명·전기설비학회논문지 Vol.24 No.10
During a ground fault the maximum fault current and neutral to ground voltage will appear at the pole nearest to the fault. Distribution lines are consisted of three phase conductors, an overhead ground wire and a multi-grounded neutral line. In this paper phase to neutral faults were staged at the specified concrete pole along the distribution line and measured the ground fault current distribution in the ground fault current, three poles nearest to the fault point, overhead ground wire and neutral line. A effect by grounding resistance of poles of ground fault current in the 22.9[kV] multi-ground distribution system. by field tests.