지중공간(地中空間)의 자연실온(自然室溫) 추정(推定)에 관(關)한 연구(硏究)
이시웅,손장열,Lee, Shi Woong,Shon, Jang Yeul 대한설비공학회 1988 설비저널 Vol.17 No.3
The purpose of this paper is to research the estimations of the indoor natural temperature in a case of the earth sheltered space and the 1st basement room in comparison with a conventional housing. The result of this study can be summerized as follows: The natural temperature of the earth sheltered house Summer : $${\theta}es=27.0+1.65sin(2{\pi}/24{\cdot}T-1.34)$$ Winter : $${\theta}ew=11.5+1.15sin(2{\pi}/24{\cdot}T-1.61)$$ The natural temperature of the 1st basement space Summer : $${\theta}us=25.5+1.00sin(2{\pi}/24{\cdot}T-1.72)$$ Winter : $${\theta}uw=13.9+1.10sin(2{\pi}/24{\cdot}T-2.29)$$ From the results of the stated above, we can calculate the cooling and heating load in the earth sheltered house and the underground space exactly and easily at Taejeon City.