http://chineseinput.net/에서 pinyin(병음)방식으로 중국어를 변환할 수 있습니다.
변환된 중국어를 복사하여 사용하시면 됩니다.
변압기 절연지 표면 금속 이물질 방전에 의한 극초단파 신호특성
윤진열,주형준,구선근,박기준,Yoon, Jin-Yul,Ju, Hyung-Jun,Goo, Sun-Geun,Park, Ki-Jun 한국전기전자재료학회 2009 전기전자재료학회논문지 Vol.22 No.10
This paper was provided to help in detecting defects in power transformer. For this purpose, a partial discharge cell was designed and manufactured as a discharge source to simulate particle defected paper-oil insulation in power transformer. Experimental set-up for measuring PD signals was described. Magnitude of electromagnetic wave signals and corresponding amount of apparent discharge were measured simultaneously against phase of applied voltage to the discharge cell. Frequency range and pattern of PRPD(Phase Resolved Partial Discharge) of partial discharge signals were examined and analyzed. The results will be contributed to build the defect database of power transformer and to decrease the substation faults.
윤진열,Yun, Jin-Yeol 한국전기기술인협회 2006 電力技術人 Vol.285 No.-
이상적인 GIS 예방진단 장비라 한다면 최소의 비용과 규모로 설치되어 결함은 빠짐없이 수 있어야 하며, 검출된 신호가 결함신호인지 잡음인지를 명확히 식별하여 필요한 정보만을 운전자에게 전달하여야 한다. 즉, 검출된 신호가 결함에 의한 것이라면 결함의 종류와 결함의 상세위치, 위험한 정도, 후속 필요조치 등에 대한 정보를 운전자에게 제공할 수 있어야 한다. 그동안 국내에서는 이상적인 기술목표를 향하여 꾸준히 연구해 왔으며 이제는 센서기술이나 센서 배치, 신호해석기술, 시스템 설계 제작기술, 시스템 운영 등에서 세계적 수준에 도달했다고 볼 수 있으나 외국에서도 마찬가지이기는 하지만 위험도 평가분야는 아직은 미흡한 상태이다. 현재 산업계와 학계, 연구계에서 연구개발을 활발히 하고 있으므로 수년 내에 만족할 수준까지 도달할 수 있을 것으로 전망된다.
윤진열,한기선,주형준,구선근,Yoon, Jin-Yul,Han, Ki-Son,Ju, Hyung-Jun,Goo, Sun-Geun 한국전기전자재료학회 2010 전기전자재료학회논문지 Vol.23 No.10
This paper describes the characteristics of electromagnetic wave propagation in power transformer. A transformer which is similar to 154 kV single phase on-site transformer unit was provided for the purpose of the experiment. The 12 dielectric windows on the transformer enclosure to install UHF (ultra high frequency) sensors and the full scale mock ups of winding and the core were also equipped in the transformer. Every sensors to be installed to the transformer was tested and verified whether they show same characteristics or not before the experiment. A discharge gap which was used as a PD (partial discharge) source moved to several necessary locations in the transformer to simulate dielectric defects. Propagation times of electromagnetic wave signal from PD source to sensors decided by the routes of both reflection phenomenon and diffraction phenomenon were compared each other. The experimental results showed propagation route of the PD signal makes an effect on the frequency spectrum of front part of the signal and the magnitude of the signal and propagation time of the signal when the signal is captured on the sensor.