LiBr용액량 변화에 따른 수평다관 흡수기의 특성 연구
권율,윤상국,Kwon, Yul,Yoon, Sang-Guk 대한설비공학회 1999 설비공학 논문집 Vol.11 No.3
An experimental study of absorption phenomena of water vapor into LiBr solution was carried out to find out the optimum solution flow rate. The staggered bundle of horizontal absorption tubes, which are the same configuration as the commercial heat pump, were tested. The results showed that the heat transfer and absorption rate were enhanced with the increase of LiBr solution flow rate. Those values for different absorber pressures showed the same qualitative trends. The optimum flow rate of solution was obtained as three times of the designed flow rate.