154 kV 변압기 보호용 비율차동계전기 오동작 방지를 위한 2고조파 억제 방식의 적용방법 및 정정값에 관한 연구
손용범(Yong-Beom Son),강상희(Sang-Hee Kang) 대한전기학회 2018 전기학회논문지 Vol.67 No.1
Inrush current and fault current in a transformer need to be distinguished from one another. In order to do this, KEPCO uses a 2nd harmonic restraint/block method. We use two setting values for 2nd harmonic restraint; 15% and 10%. We also apply per-phase blocking method among various harmonic restraint methods. If the transformer is located at the radial system, we adjust 10% in the 2nd harmonic restraint, but this method is not enough to prevent mal-operations of the current differential relay and let us spend more time to change setting value again as the power system changes. In this paper, a more reasonable setting value for a 2nd harmonic blocking scheme in KEPCO is proposed. To present a proposed method, the fault data of the current differential relays which have occurred since 2009 are analyzed. To evaluate the performance of the proposed method, the results of the RTDS test for the current differential relay of the transformer by KEPCO are analyzed.
가공 송전선로 크레인 접촉에 의한 보호계전기 동작 사례분석
박지환(Ji-Hawn Park),박진만(Jin-Man Park),이재청(Jae-cheong Lee),최종기(Jong-Ki Choi),손용범(Yong-Beom Son),장우일(Woo-il Jang) 대한전기학회 2021 대한전기학회 학술대회 논문집 Vol.2021 No.4
가공 송전선로는 공사용 크레인 또는 수목 등과의 접촉이나 근접으로 인하여 미소전류의 아크를 동반하는 고저항 지락사고가 종종 발생한다. 본 논문은 실제 현장에서 발생한 크레인 접촉 고장사례를 설비부서 고장보고서 및 송전선로 보호계전기의 동작파형을 활용하여 그 현상을 분석하였다.