지중온도회복을 고려한 지열 히트펌프 시스템의 운전방법 검토
배상무(Sangmu Bae),전재영(Jae-Young Jeon),권영식(Young Sik Kwon),남유진(Yujin Nam) 한국지열·수열에너지학회 2020 한국지열에너지학회논문집 Vol.16 No.4
Ground source heat pump (GSHP) systems are actively introduced as cooling and heating conditioning systems of buildings due to annual stable performance and easily maintenance. However, ground temperature imbalance is occurred when the GSHP is used for a long period. Therefore, in this study, we proposed the operation method of the system that considered the recovery time of heat source temperature. The entering water temperature (EWT) and heat exchange rate (HER) were comparatively analyzed according to the continuous and intermittent operation. Furthermore, the underground thermal environment was evaluated by numerical analysis model. As the result, the intermittent operation was a maximum of 12.3% higher HER during the heating period than the continuous operation. In addition, the overall ground heat source temperature at the intermittent operation was higher than it at the continuous operation.