상변화물질(PCM)을 이용한 열교환기용 동파방지밸브에 관한 실험적 연구
윤재호(Yun, Jea-ho),김종하(Kim, Joung-ha),정순영(Jeong, Soon-young),양윤섭(Yang, Yoon-sub),김성현(Kim, Seong-Hyun),송덕용(Song, Duk-yong) 한국태양에너지학회 2012 한국태양에너지학회 논문집 Vol.32 No.6
This paper is an experimental study on the freezing protection valve used for solar water heating, air-conditioning systems, and plumbing systems. When the phase change occurs from liquidto solid, most of the substances except water volumetrically shrink. And referred to as PCM(Phase Change Material)a substance with such properties, the phase change temperature varies depending on the material. To prevent the freezing of the plumbing system, such as air-conditioning system in the winter season, we developed a several types of freezing protection valve using PCM whose freezing temperature are 2-4℃. The working principle of the freezing protection valve is that the fluid inside the pipe is released to prevent the system-collapse when fluid temperature reaches the freezing temperature of the PCM. And then the valve is closed and returned to the original position automatically when the temperature of the operating fluidrises. In this paper, the operating temperatures, discharge flow rate and the response characteristics of the valve during the operation are tested and investigated. From the results of this research the freezing protection valves employing PCM are expected to be commercialized in the near future.
김민준(Min-Jun Kim),김종하(Joung-Ha Kim),윤재호(Jae-Ho Yun),박일환(Il-Hwan Park),이규칠(Kyu-Chil Lee) 대한설비공학회 2007 설비공학 논문집 Vol.19 No.11
In this study, ice slurry generator using air cylinder was designed and manufactured to investigate the heat transfer characteristic of the ice slurry generator. The ice slurry generator has the same shape as the shell-and-tube type heat exchanger. Refrigerant is flowing in the shell side and ethylene glycol solution in the tube side. The experiment was conducted on performance of ice slurry generator using air cylinder with standard condition and the results are plotted on the time scale. The experimental tests on the various concentration of ethylene glycol solution, the various solution velocity in the tube side and the various tube size have been carried. For the above experimental conditions, ice making characteristics of the ice slurry generator are evaluated in terms of the overall heat transfer coefficient. And the experimental results show that the overall heat transfer coefficient of the system is increased as the tube size and the concentration of ethylene glycol decreases.
PCM을 적용한 자연대류형 수냉식 방열기의 냉각특성에 관한 실험적 연구
성대훈(Dae-Hoon Sung),김종하(Joung-Ha Kim),윤재호(Jae-Ho Yun),김우승(Woo-Seung Kim),백종현(Jong-hyeon Peck) 대한설비공학회 2008 대한설비공학회 학술발표대회논문집 Vol.2008 No.2
The liquid cooling effect of a natural convection type radiator by using the PCM has been investigated experimentally. The radiator size is 423×295×83 ㎜ and PCM container size is 398×270×26 ㎜. The objective is elapsed time higher than maximum time to reach for maximum operating temperature of a general liquid cooling radiator. This study, in order to study on the effects of the phase-change phenomenon, carried out the various mass flow rate, input electric power, ambient and melting point of three type PCM. For the above experimental parameter, the melting time was performed about 180/250/560 min at input power 150 W and ambient 30℃ from using the three type PCM(PCM_S1/S2/S3) respectively. Furthermore, the effects of the thermal dissipation was decreased higher input power than lower input power at heating block and melting time of PCM. However, the effects of mass flow rate did not nearly affect of the thermal performance especially.
김민준(Min-Jun Kim),김종하(Joung-Ha Kim),윤재호(Jae-Ho Yun),박일환(Il-Hwan Park),조형석(Hyoug-Seok Cho),안성국(Seong-Kuk An) 대한기계학회 2007 대한기계학회 춘추학술대회 Vol.2007 No.5
In this study, Ice slurry generator heat transfer characteristics are experimentally investigated for the ice slurry generating system with scraper which is pneumatically operated. The ice slurry generator has the same shape as the vertical double tube type heat exchanger. Refrigerant is flowing in the outside tube and ethylene glycol solution in the inside tube. Refrigerant and solution water are parallel flow type which entering bottom of generator and leaving top of generator. The experimentations are conducted under the various test conditions such as compressor speed and cooling water temperature. For the above experimental conditions, heat transfer characteristics of the ice slurry generating system are evaluated in terms of the overall heat transfer coefficient and the heat transfer rate. And the experimental results show that the heat transfer rate of the system is increased as the compressor speed increases and the cooling water temperature decreases.
공압구동형 슬러리아이스 제빙기의 제빙특성에 관한 실험적 고찰
김민준(Min-Jun Kim),김종하(Joung-Ha Kim),윤재호(Jae-Ho Yun),권오경(Oh-Kyung Kwon),이규칠(Kyu-Chil Lee),박일환(Il-Hwan Park),양윤섭(Yun-Sub Yang) 한국태양에너지학회 2006 한국태양에너지학회 학술대회논문집 Vol.- No.-
In this study, ice making characteristics are experimentally investigated for the ice slurry generating system which is pneumatically operated. The ice slurry generator has the same shape as the shell-and-tube type heat exchanger. Refrigerant is flowing in the shell side and ethylene glycol solution in the tube side. The experimentations are conducted under the various test conditions such as aqueous solution concentration, flow rate of solution and frequency of cylinder stroke. For the above experimental conditions, ice making characteristics of the slurry ice generating system are evaluated in terms of the overall heat transfer coefficient and the amount of slurry ice generation. And the experimental results show that the heat transfer rate of the system is increased as the flow rate of aqueous solution increases and the concentration of ethylene glycol decreases.