Zhi-ting Zhou,Zhen-nan Fan,Jian-fu Li,Kun Wen,Bide Zhang,Tao Wang,Yan-kun Xia,Zhang Sun,Bing Yao 대한전기학회 2018 Journal of Electrical Engineering & Technology Vol.13 No.6
A field-circuit coupling model of a typical faulty generator is established to correct through-bolt end-region overheating and breakdown failure in a tubular hydro-generator. Using the model, eddy current loss and electromagnetic forces on through bolts under normal and failure conditions are analyzed and compared and the natural frequency of a through bolt is determined. Based on the analysis results, the causative mechanism of failure is revealed and targeted improvement design measures are proposed. The numerical results are found to be consistent with the actual fault characteristics, validating the design measure improvements. The results are useful in improving the design and manufacturing standards and enhancing the operational reliability of large tubular hydrogenerators.
Zhou, Zhi-ting,Fan, Zhen-nan,Li, Jian-fu,Wen, Kun,Zhang, Bide,Wang, Tao,Xia, Yan-kun,Sun, Zhang,Yao, Bing The Korean Institute of Electrical Engineers 2018 Journal of Electrical Engineering & Technology Vol.13 No.6
A field-circuit coupling model of a typical faulty generator is established to correct through-bolt end-region overheating and breakdown failure in a tubular hydro-generator. Using the model, eddy current loss and electromagnetic forces on through bolts under normal and failure conditions are analyzed and compared and the natural frequency of a through bolt is determined. Based on the analysis results, the causative mechanism of failure is revealed and targeted improvement design measures are proposed. The numerical results are found to be consistent with the actual fault characteristics, validating the design measure improvements. The results are useful in improving the design and manufacturing standards and enhancing the operational reliability of large tubular hydro-generators.
Kun Wen,Li Han,Zhi-ting Zhou,Zhen-nan Fan,Yong Liao,Jun Wang,Zhang Sun,Bing Yao,Bide Zhang 대한전기학회 2019 Journal of Electrical Engineering & Technology Vol.14 No.3
To obtain more precise and rational calculation details of the loss and heat of a damper winding in a tubular hydro-generator, this study develops a three-dimensional, fi nite-element, electromagnetic-temperature fi eld close-coupling model of the damper winding. On the basis of multi-physical fi eld coupled theory, the model fully considers the temperature eff ects of the damper winding resistivities and heat conductivities, and the eddy current loss in the end region of the damper winding. The model was verifi ed by direct tests of the damper winding temperature. Unlike the conventional weak-coupling model, the proposed close-coupling model fully captures the interaction between the electromagnetic and temperature fi elds. Therefore, of the model more accurately and reasonably calculates the loss and heat of the damper winding than the conventional model. The proposed calculation model can properly assess the loss and heat of damper windings in large hydro-generators, which is helpful for improving the design standards of hydro-generators.