각층 공조방식이 적용된 병실에 있어서 공기오염의 확산 및 제거
성민기(Min-Ki Sung),카토신스케(Shinsuke Kato),김종훈(Jong-Hun Kim) 한국생활환경학회 2012 한국생활환경학회지 Vol.19 No.1
This study verified the hazard of contaminant dispersion using an experiment in a hospital where multi zone variable air volume (VAVs) systems were being operated for multiple ward areas. The results showed that the contaminant released in a source ward was dispersed to all other wards through the air conditioning system, although the concentration were decreased through dilution with outdoor air. Then airborne bacteria and fungi were measured in the ward area where was occupied by patients. The results indicated that the sources of airborne microbes were in the ward and they were assumed to be patients. However, the microbes were successfully removed by the air filters in the air conditioning system before supplied to each ward. Further consideration on the methods to minimize the airborne dispersion before removed in air conditioning systems is required.