TRNSYS 를 이용한 해수열원 히트펌프의 연간 난방성능 모사
백영진(Young-Jin Baik),이승호(Seung Ho Lee),김민성(Minsung Kim),이영수(Young-Soo Lee),장기창(Ki-Chang Chand),나호상(Ho-Sang Ra) 대한기계학회 2012 대한기계학회 춘추학술대회 Vol.2012 No.11
In this study, an annual heating performance of a seawater-source heat pump, assumed installed in Gangneung city near the East Sea in Korea, was simulated. An annual heating load for a typical Korean-style apartment house, which has an effective area of about 85 ㎡, was modeled by using TRNSYS program. The seawater temperature was calculated from the regression equation based on the measurement. A heat pump performance at full-load was calculated from the regression equation, which involves refrigerant’s evaporating and condensing temperatures, based on a commercial compressor performance map. A part-load performance was also considered. Simulation results show that an annual heating coefficient of performance (COP<SUB>H</SUB>) of a seawater-source heat pump is approximately 3.3 and that it is necessary to improve part-load performance to increase an annual performance of the heat pump.