http://chineseinput.net/에서 pinyin(병음)방식으로 중국어를 변환할 수 있습니다.
변환된 중국어를 복사하여 사용하시면 됩니다.
신동걸(Dong-keol Shin),김은수(Eun-su Kim),이진욱(Jin-uk Lee),이상일(Sang-il Lee),이형기(Hyong-ki Lee),황광일(Kwang-il Hwang) 한국항해항만학회 2008 한국항해항만학회 학술대회논문집 Vol.2008 No.공동학술
The purpose of this study is to measure out-surface temperatures of a newly-launched 6,700 tonnage training ship for each season from July 2007 to April 2008. The solar heat gain is important factor in indoor thermal loads and HVAC. Different thermal conditions are measured in the port side and the starboard side with the locations of the sun.
연구ㆍ사무공간의 냉난방용으로 설치된 400RT급 수직형 지열시스템의 봄철 성능평가
신동걸(Dong-Keol Shin),김중헌(Joong-Hun Kim),신승호(Seung-Ho Shin),황광일(Kwang-Il Hwang) 한국지열·수열에너지학회 2008 한국지열에너지학회논문집 Vol.4 No.2
400RT geothermal system which is consist with vertical-typed 112 geothermal heat exchangers is measured and evaluated in spring, 21st~24th May 2008. As the results, the average temperature difference between inlet and outlet of geothermal pipes is 1~2℃ and that of cool water supply is 2~6℃, when being normally operated. Despite temperature fluctuations by cooling loads, the average temperature difference between main pipes of inlet and outlet of geothermal heat exchangers is measured as 3℃. The geothermal system COPs are calcluated as 2.92 ~ 3.92 in every 12 hours.
신동걸(Dong-keol Shin),한동훈(Dong-hoon Han),우상우(Sang-woo Woo),이진욱(Jin-wook Lee),이형기(Hyeng-ki Lee),황광일(Kwang-il Hwang) 한국마린엔지니어링학회 2007 한국마린엔지니어링학회 학술대회 논문집 Vol.2007 No.-
At the points of the labor environment related to the productivity and the health care of the crewmen, the control of the indoor air quality(IAQ) on a ship is very important, because crewmen are working and living in a air-tighter indoor spaces of a ship than those of buildings on the land. In this paper, TYOC, HCHO are measured as the barometer of indoor air quality of a newly-launched 6,700 tonnage training ship. On measuring processes, it is cleared that the indicated IAQ values are almost below the legal limits except special affairs.
신동걸(Dong-keol Shin),한동훈(Dong-hoon Han),우상우(Sang-woo Woo),이진욱(Jin-wook Lee),이형기(Hyeng-ki Lee),황광일(Kwang-il Hwang) 한국마린엔지니어링학회 2007 한국마린엔지니어링학회 학술대회 논문집 Vol.2007 No.-
The purpose of this study is to measure a thermal conditions of the various cabins in a newly-launched 6,700 tonnage training ship. The temperature, humidity, air supply volume of each cabins' are measured. On measuring processes, it is cleared that the inner conditions are not within the comfort area proposed by ASHRAE, mainly because of the low humidities indicated below 25%.
신동걸(Dong-keol Shin),김은수(Eun-su Kim),이진욱(Jin-uk Lee),이상일(Sang-il Lee),이형기(Hyong-ki Lee),황광일(Kwang-il Hwang) 한국마린엔지니어링학회 2008 한국마린엔지니어링학회 학술대회 논문집 Vol.2008 No.-
The purpose of this study is to measure out-surface temperatures of a newly-launched 6,700 tonnage training ship fur each season from July 2007 to April 2008. The solar heat gain is important factor in indoor thermal loads and HVAC. Different thermal conditions are measured in the port side and the starboard side with the locations of the sun.
신동걸(Dong-keol Shin),우상우(Sang-woo Woo),이진욱(Jin-wook Lee),이형기(Hyeng-ki Lee),황광일(Kwang-il Hwang) 한국마린엔지니어링학회 2007 한국마린엔지니어링학회 학술대회 논문집 Vol.2007 No.-
The purpose of this study is to measure a thermal conditions of the various cabins in a newly-launched 6,700 tonnage training ship. The temperature, humidity, air supply volume of each cabins' are measured. On measuring processes, it is cleared that the inner conditions are within the comfort area proposed by ASHRAE, but each cabins are measured that temperature distribution is different. Especially saloon is measured to low temperature as 19℃.
김은수(Eun-su Kim),신동걸(Dong-keol Shin),이진욱(Jin-uk Lee),이상일(Sang-il Lee),이형기(Hyong-ki Lee),황광일(Kwang-il Hwang) 한국마린엔지니어링학회 2008 한국마린엔지니어링학회 학술대회 논문집 Vol.2008 No.-
The purpose of this study is to analyze the measured thermal conditions of the various cabins in a newly-launched 6,700 tonnage training ship on each season. The temperature, humidity, air supply volume of each cabins' are measured. On Analyzing processes, it is cleared that this ship is possible to control temperature within ASHRAE comport condition area, but humidity is different. So, the study about the controling humidity is needed in future.