http://chineseinput.net/에서 pinyin(병음)방식으로 중국어를 변환할 수 있습니다.
변환된 중국어를 복사하여 사용하시면 됩니다.
고희석(Hee-Seog Koh),김성삼(Sung-Sam Kim),김주찬(Ju-Chan Kim),최종규(Jong-Kyu Choi) 한국조명·전기설비학회 2006 한국조명·전기설비학회 학술대회논문집 Vol.2006 No.11월
In this paper, we make an experiment on the efficient construction method of plate electrode and the influence of electric potential interference in plate electrode, and building foundation. The experimental result of electric potential measurement is taken in the basis of movement direction and the condition laying plate electrode underground in building foundation. It shows that the vertical laying construction method exhibits more efficient reduction of electric potential rising in diagonal direction and X axis than horizontal laying construction method.
고희석(Hee-Seog Koh),신수한(Su-Han Shin),김주찬(Ju-Chan Kim),최종규(Jong-Gyu Choi) 한국조명·전기설비학회 2004 한국조명·전기설비학회 학술대회논문집 Vol.2004 No.11월
There are many electricity, electronics, and communication equipment which need to Grounding in the building. When electric current flows into a certain Grounding system in the same building, the potential of other Grounding system rises. This potential interference require surface potential of electrods by electrode shape. In this paper basic formula is deduced on the basis of both electrodes surface potential of Grounding electrode as a source of the potential interference and Grounding electrode which receive the potential interference. The degree of potential interference as multiple Grounding electrode is verified the simulated results by means of the simple model in advance.