http://chineseinput.net/에서 pinyin(병음)방식으로 중국어를 변환할 수 있습니다.
변환된 중국어를 복사하여 사용하시면 됩니다.
직접접촉식 LNG기화기 응용을 위한 칼럼 열교환기 기포특성에 관한 연구
김성종,한승탁,김종보,Kim, S.J.,Han, S.T.,Kim, J.B. 대한설비공학회 1991 설비공학 논문집 Vol.3 No.2
In the present investigation, it has been proposed to utilize a direct contact heat exchanger as an evaporator to solve the difficulties such as scaling, corrosion and law thermal efficiencies, associated with the conventional evaporator. Liquified nitrozen was utilized as a working fluid to investigate basic natures of bubble dynamics in the evaporator, and spray nozzles were adopted to inject liquified nitrozen into the spray column with varying flow rates of dispersed phase fluids. Experimentations were carried out in the range of $6.54{\times}10^{-4}kg/s$ - 0.030 kg/s for dispersed phase flow rates with one, three and five nozzle holes. Observing the bubble dynamics for the evaporator the feasibility of utilizing a direct contact heat exchanger as a LNG evaporator has been evaluated. The results show that no eruption phenomena was observed in the present investigation with $LN_2$ and the interface between $N_2$ bubbles and water was fully turbulent. It is believed that the high injection velocity of $LN_2$ through the spray nozzles provide good mixing effects for both heat and mass transfers between water and $N_2$ bubbles. Ice was formed on the surface of the spray nozzle for higher $LN_2$ flow rates. However, even in this case, it is observed that the ice was detached as soon as it was formed. Under the present experimental conditions, the shapes of $LN_2$ bubbles were in the spherical-cap region according to the Clift, Grace and Weber Graphs. The height of foam region caused by the breakup of larger bubbles keeps increasing with high injection velocities until it reaches it's maximum height.
증기응축용 직접접촉식 열교환기의 냉각수 유량과 내부압 변화에 따른 열전달 특성연구(LNG 기화기와의 조합목적)
이병철,한승탁,김종보,Lee, B.C.,Han, S.T.,Kim, C.B. 대한설비공학회 1991 설비공학 논문집 Vol.3 No.3
Heat transfer characteristics of a direct contact heat exchanger utilizing sieve trays and spray nozzles for steam condensation for the purpose of combining with a LNG evaporator have been investigated with various cooling water flow rates and different vacuum pressures within the heat exchanger for the purpose of steam condensation. Temperature profiles and the volumetric overall heat transfer coefficients in a direct contact heat exchanger have been obtained for comparisons. The results show that the temperature differences between cooling water and steam along the direct contact heat exchanger height are rapidly decreasing and the volumetric overall heat transfer coefficients of the exchanger improves greatly as the inside vacuum pressure increases. The values of the overall heat transfer coefficients at P=-680mmHg have been increased significantly compared with at atmospheric pressure. At given pressure conditions, it is found that the values of average volumetric overall heat transfer coefficients for the sieve tray are found to be approximately 10% higher than those of the spray nozzle.