http://chineseinput.net/에서 pinyin(병음)방식으로 중국어를 변환할 수 있습니다.
변환된 중국어를 복사하여 사용하시면 됩니다.
김두천,최진희,원영수,Kim, D.C.,Choi, J.H.,Won, Y.S. 대한설비공학회 1989 설비공학 논문집 Vol.1 No.3
The ASHRAE Simplified Energy Analysis Procedure using the Modified Bin Method(SEAP) is compared with the hourly calculation program, HASP/ACLD. The HASP/ACLD model office building with VAV system in Seoul is used as the basis for comparison. And the parameters considered are glass to wall area ratio and internal heat gains. The results show that SEAP predictions of annual energy use agree with HASP/ACLD predictions within 5% deviation. But there is a large difference in cooling and heating energy as glass to wall area ratio is varied. The SEAP cooling energy is 65-85% and the heating energy is 104-160% of the HASP/ACLD results. This is probably due to the solar heat gain data. the data related to the SEAP must be developed prior to use it.