http://chineseinput.net/에서 pinyin(병음)방식으로 중국어를 변환할 수 있습니다.
변환된 중국어를 복사하여 사용하시면 됩니다.
남석호,홍종기,허정일,강형구,Nam, Seok-Ho,Hong, Jong-Gi,Heo, Jeong-Il,Kang, Hyoung-Ku The Korean Superconductivity Society 2012 Progress in superconductivity Vol.13 No.3
Studies on the development of high voltage superconducting apparatuses, such as transmission superconducting fault current limiters (SFCLs) and superconducting cables, have been performed worldwide. In this paper, a study on the electrical insulation characteristics of electro negative gas according to various pressures and utilization factors was conducted as a part of developing a high voltage superconducting coil with a sub-cooled nitrogen cooling system. Some gases such as helium (He), nitrogen ($N_2$), and sulfur hexafluoride ($SF_6$) are considered for pressurizing the sub-cooled nitrogen cooling system of high voltage SFCLs and superconducting cables. $SF_6$ is used to pressurize and enhance the dielectric performance of a superconducting system of a sub-cooled nitrogen cooling system for superconducting cables being developed in the Republic of Korea. In this paper, dielectric experiments on AC voltage, as well as lightning impulse voltage of $SF_6$, are conducted according to various utilization factors by using several kinds of sphere-to-plane electrode systems. As results, it is known that the empirical formulae of $SF_6$, known as an electro negative gas, are derived according to various pressures and utilization factors. Also, the appropriate pressure condition for designing a high voltage superconducting coil is found from the viewpoint of dielectric performance.
친환경 고압배전반 개발을 위한 dry air의 압력별 절연내력특성 분석에 관한 연구
남석호(Seok Ho Nam),강형구(Hyoungku Kang) 대한전기학회 2011 전기학회논문지 Vol.60 No.8
The environmental pollution caused by green-house gases such as CO₂ and SF6 has been becoming the main issue of industrial society. Many developed countries are making efforts to minimize the amount of CO₂ emission come from the operation of high voltage electrical apparatuses. As a part of these efforts, 180 countries signed the Kyoto Protocol in 1997 to cut back on their green-house gas emissions. Nowadays, the study on the development of dry air insulated switchgear (DAIS) which is known as an eco-friendly electrical apparatus is in progress. A DAIS is advantageous for minimizing the effect of impurities and enhancing the dielectric characteristics over an air insulated switchgear (AIS) by applying constant pressure to an enclosed cubicle. Therefore, a study on the electrical insulation performance of dry air as a gaseous insulation medium is conducted in this paper to substitute a gas insulated switchgear (GIS) for DAIS. As results, it is verified that the AC dielectric characteristics of dry air are similar to those of air and the lightning impulse dielectric characteristics of dry air are superior to those of air at 1bar pressure condition. However, dry air is of inferior dielectric characteristics to SF6 at 4bar pressure condition. Finally, it is suggested that the internal pressure of DAIS should be over 4bar pressure to develop a high voltage switchgear which has similar electrical performance to a conventional GIS. Also, the empirical formulae on calculating the maximum electric field intensity at sparkover of dry air are deduced by experiments according to pressures. It is expected that these results are helpful to design and develop a high voltage electrical apparatus.
고전압 전력기기 개발을 위한 기중 절연파괴특성 분석에 관한 연구
남석호(Seok Ho Nam),강형구(Hyoungku Kang) 대한전기학회 2011 전기학회논문지 Vol.60 No.5
The accidents caused by dielectric instability have been increasing in power grid. It is important to enhance the dielectric reliability of a high voltage apparatus to reduce the damage from electrical hazards. To develop an electrically reliable high voltage apparatus, the experimental study on the electrical breakdown field strength is indispensable, as well as theoretical approach. In this paper, the lightning impulse breakdown characteristics considering utilization factors are studied for the establishment of insulation design criteria of an high voltage apparatus. The utilization factors are represented as the ratio of mean electric field to maximum electric field. Dielectric experiments are performed by using several kinds of sphere-plane electrode systems made of stainless steel. As a result, it is found that dielectric characteristics are affected by not only maximum electric field intensity but also utilization factors of electrode systems. The results are expected to be applicable to designing the air-insulated high voltage apparatuses.