http://chineseinput.net/에서 pinyin(병음)방식으로 중국어를 변환할 수 있습니다.
변환된 중국어를 복사하여 사용하시면 됩니다.
단일굴곡 및 이중굴곡 판 형상을 갖는 직교류 공랭식 판형열교환기의 전열특성에 대한 실험적 연구
김민성(Minsung Kim),백영진,박성룡(Seong-Ryong Park),나호성(Ho-Sang Ra),정재훈(Jae Hoon Jeong),임혁(Hyug Lim),Jae-Hoon Lee 대한설비공학회 2009 설비공학 논문집 Vol.21 No.6
Experimental study on a cross-flow air-cooled plate heat exchanger (PHE) was performed. Two types of PHEs were manufactured either with single-wave plates or with double-wave plates in parallel. Cooling air flows through the PHEs in a crosswise direction against internal hot water. The heat exchanger aims to substitute open-loop cooling towers with closed-loop water circulation, which guarantees cleanliness and compactness. In this study, prototype single-wave and double-wave PHEs were designed and tested in a laboratory scale experiments. From the tests, the double-wave PHE shows approximately 50% enhanced heat transfer performance compared to the single-wave PHE. However, the double-wave PHE costs 30% additional pressure drop. For the commercialization, a wide channel design for air flow would be essential for performance and reliability