Song, Hwachang,Vovos, Panagis N.,Cho, Kang-Wook,Kim, Tae-Sun The Korean Institute of Electrical Engineers 2016 Journal of Electrical Engineering & Technology Vol.11 No.1
This paper presents a method of decision on where bus splitting is needed to reduce fault current level of power systems and to satisfy the fault current constraints. The method employs a modified fault current constrained optimal power flow (FCC-OPF) with X variables for the candidate locations of splitting and for decision making on whether to split or not, it adopts soft-discretization by augmenting inversed U-shaped penalty terms. Also, this paper discusses the procedure on the adequate selection of bus splitting locations based on the results of the modified FCC-OPF, to reduce the total number of the actions taken.
Hwachang Song,Panagis N. Vovos,Kang-Wook Cho,Tae-Sun Kim 대한전기학회 2016 Journal of Electrical Engineering & Technology Vol.11 No.1
This paper presents a method of decision on where bus splitting is needed to reduce fault current level of power systems and to satisfy the fault current constraints. The method employs a modified fault current constrained optimal power flow (FCC-OPF) with X variables for the candidate locations of splitting and for decision making on whether to split or not, it adopts soft-discretization by augmenting inversed U-shaped penalty terms. Also, this paper discusses the procedure on the adequate selection of bus splitting locations based on the results of the modified FCC-OPF, to reduce the total number of the actions taken.