http://chineseinput.net/에서 pinyin(병음)방식으로 중국어를 변환할 수 있습니다.
변환된 중국어를 복사하여 사용하시면 됩니다.
Experimental Verification for Active Power Filter based Four-Leg Inverter with SUI-PI Controller
El-sotouhy Mohamed M.,Mansour Ahmed A.,Marei Mostafa I.,Zaki Aziza M.,EL-Sattar Ahmed A. 대한전기학회 2021 Journal of Electrical Engineering & Technology Vol.16 No.5
Four-leg active power fi lter (4-LAPF) is considered one of the vital active fi lters that are frequently used in industrial applications, especially those that need to be controlled in each phase. In addition to control the neutral current that is created because of unbalanced and non-linear loads. In this paper, the active fi lter is controlled by a proposed control method that can achieve simplicity and intelligence at the same time. The novelty of this paper is simulation and experimental verifi cation for the proposed controller with 4-LAPF. This controller relies on instantaneous reactive power theory, which is used to create the reference currents for the 4-LAPF to inject into the network to mitigate problems associated with unbalanced and non-linear loads. As a result, the supply current is maintained a pure sinusoidal wave. The system is simulated using Matlab/Simulink and experimentally verifi ed. The simulation and experimental results prove the preference of the proposed controller over the conventional proportional-integration controller, where it reduces the total harmonic distortion of the supply current and enhance the power quality.