Effects of the Insulation Quality on the Frequency Response of Power Transformers
Abeywickrama Nilanga,Ekanayake Chandima,Serdyuk Yuriy V.,Gubanski Stanislaw M. The Korean Institute of Electrical Engineers 2006 Journal of Electrical Engineering & Technology Vol.1 No.4
This paper presents results of frequency domain spectroscopy (FDS) measurements on oil-impregnated pressboard insulation, their analyses and use of the data for modeling high frequency response (FRA) of transformers. The dielectric responses were measured in a broad frequency range, i.e. from 0.1 mHz to 1 MHz, on model samples containing different amount of moisture. The responses were parameterized with terms representing dc conductivity, low frequency dispersion and Cole-Cole polarization mechanisms and they were thereafter used to model the FRA response of a three-phase transformer.
Effects of the Insulation Quality on the Frequency Response of Power Transformers
Nilanga Abeywickrama,Chandima Ekanayake,Yuriy V. Serdyuk,Stanislaw M. Gubanski 대한전기학회 2006 Journal of Electrical Engineering & Technology Vol.1 No.4
This paper presents results of frequency domain spectroscopy (FDS) measurements on oil-impregnated pressboard insulation, their analyses and use of the data for modeling high frequency response (FRA) of transformers. The dielectric responses were measured in a broad frequency range, i.e. from 0.1 m㎐ to 1 ㎒, on model samples containing different amount of moisture. The responses were parameterized with terms representing dc conductivity, low frequency dispersion and Cole-Cole polarization mechanisms and they were thereafter used to model the FRA response of a three-phase transformer.