한경전,김진문,전화성,이경우,Han, Geung-Jeon,Kim, Jin-Mun,Jeon, Hwa-Sung,Lee, Kyung-Woo 제어로봇시스템학회 2011 제어·로봇·시스템학회 논문지 Vol.17 No.6
In this paper, we standardized the water operation system picture, process control logic, realtime database and system configuration. All aspects, including monitoring & controlling processes, symbols such as pumps, valves and pipes were standardized. As a result we have developed a specialized Integrated water operation system, iWater. We have developed a variety of advanced application programs that are essential for water treatment systems, such as IWS (Integrated Warning system), MBO(modbus opc)/LSE(LS ethernet) driver, video monitoring, self diagnosis system, network monitoring, etc. IWS prevents water supply accidents by using a variety of alarms and warning messages. Drivers have the flexibility to communicate with other 3rd party systems. We expect that iWater will eliminate any concerns regarding water-related issues while also promoting the production and fair distribution of clean water.
전항배,손광익,이태용,한경전 대한상하수도학회 1995 상하수도학회지 Vol.9 No.4
An improving example for traditional rapid mix system was studied in the base of mechanisms of alum coagulation. Local status of the major water treatment plants was also investigated and evaluated for upgrading these plants. A new design and operating criterium for rapid mix system was proposed to velocity gradient, G of 1,000-1,500 sec^-1 and detention time, t of 1 sec from the results of experiments and literature reviews. Comparing the present rapid mix system to this criterium, apparent difference existed between them. In this study, for improving Seongnam water treatment plant, a design criterium of velocity gradient, and detention time was set to 1,100 sec^-1, 1 sec, respectively. A new rapid mix system adopted the nozzle injection countcurrently cross the inlet pipe to the whole area. The injection velocity was 17m/s, nozzle diameter was 1.0mm, and number of nozzle was 70. The new modified system without running present four 75 HP agitators was able to improve water quality(based on sedimentation effluent) by 15-35% and to reduce electrical energy by 98%.