22.9kV-y 수전 수용가 접지시스템의 지락고장전류 분류율
이주철(Ju-Cheol Lee),이태욱(Tae-Wook Lee),남아영(Ah-Young Nam),유홍국(Hong-Guk You) 한국조명·전기설비학회 2021 한국조명·전기설비학회 학술대회논문집 Vol.2021 No.11
This paper, although the 22.9 kV neutral multi-grounding distribution line has a large ground fault current, only a part of the fault current caused by a single line-to-ground fault current into the earth through the earth electrode close to the fault point, and the rest is return to the neural point of the power source through the multi-grounded neutral and earth. As a result of comparative analysis of document and actual measurement cases for the current split rate of the 22.9 kV multi-grounding distribution line, it was confirmed that there are many differences from the split rate generally applied in the substation grounding design.