박만홍(M. H. Park),김광추(K. C. Kim),김경훈(K. H. Kim) 대한기계학회 2003 대한기계학회 춘추학술대회 Vol.2003 No.4
Numerical analysis is carried out to assess the temperature distribution on the mixing tee line of Residual<br/> Heat Removal System (RHRS). In RHRS, hot and cold fluids of main and bypass piping are mixed and<br/> unmixed by the flow rate or piping layout. Thermal stratification phenomenon is a cause of major degradation<br/> on RHRS piping. According to the analysis for each operation modes, maximum temperature difference<br/> between top and bottom of piping were evaluated about 60K when the flow rate of main and bypass lines is<br/> same. Temperature difference will be decreased at the elbow on RHRS piping if the length of vertical piping<br/> is increased.
전력구내 지중케이블 강제냉각에서의 적정냉각구간에 관한 연구
이재헌,정상호,김재근,박만홍,Lee, J.H.,Chung, S.H.,Kim, J.G.,Park, M.H. 대한설비공학회 1990 설비공학 논문집 Vol.2 No.1
The forced cooling system has been widely applied to passing more electric current in the underground power transmission cable technology. In this paper, the optimum cooling span of the in-trough-indirect water cooling method within an electric tunnel was investigated. A parametric study was performed for the cable currents, the coolant flow rates, and the coolant inlet temperatures. As a result, the temperature of the inlet air has been found as the most important parameter in determination of the optimum cooling span.