This study progressed to survey formaldehyde (HCHO) concentration at using passive sample for 5 days and active sampler for 1 hr in new building. We selected places such as department office, lecture room, professor`s room, studio room, and hallway. T...
This study progressed to survey formaldehyde (HCHO) concentration at using passive sample for 5 days and active sampler for 1 hr in new building. We selected places such as department office, lecture room, professor`s room, studio room, and hallway. The highest average concentration of HCHO was 544.13 ㎍/m3 at active sampler in studio room. Whereas lowest average concentration of formaldehyde was 4.91 ㎍/m3 at active sampler in hall way. Specially HCHO concentration of the studio room was more than 8 times on the indoor air quality standard, and concentration of the remaining places are above the standard. These results can be explained that indoor air quality of new building should be improved by installing the air cleaning device and ventilation system.