This study has been conducted to evaluate the applicability of the control method in the dehumidification-integrated radiant floor cooling system in terms of stability of the room air temperature and the control variables through experiments. To do th...
This study has been conducted to evaluate the applicability of the control method in the dehumidification-integrated radiant floor cooling system in terms of stability of the room air temperature and the control variables through experiments. To do this, the relationship between the control variables in preventing floor surface condensation is first analyzed and the control method is predetermined through simulations. The results are as follows. First, it is necessary to determine the operation status of the dehumidification system according to the relationship between floor surface temperature and dew point temperature in the conditioned space. Second, outdoor reset with indoor temperature feedback control is better than on/off bang-bang control with respect to temperature stability in controlling the room air temperature and the possibility of energy savings. Finally, the humidity sensor can be located with the current thermostat in that there are small differences in absolute humidity in vertical distribution.