In this paper the transformer loss reduction is studied by way of connecting in series the parallel running transformer at light load and connecting in parallel as it is at heavy load.
As a result of this experiment, it is proved that the loss reduc...
In this paper the transformer loss reduction is studied by way of connecting in series the parallel running transformer at light load and connecting in parallel as it is at heavy load.
As a result of this experiment, it is proved that the loss reduction come to be 52 percentage when the transformer operates in no load and 27 percentage in light load operation of transformer.