      저주파 접지임피던스 측정에 미치는 보조전극의 영향 = Effects of Auxiliary probe on Low Frequency Ground Impedance Measurement

      한글로보기

      https://www.riss.kr/link?id=A76344278

      • 0

        상세조회
      • 0

        다운로드
      서지정보 열기
      • 내보내기
      • 내책장담기
      • 공유하기
      • 오류접수

      부가정보

      다국어 초록 (Multilingual Abstract)

      In this paper, the effects of the position and the angle of the auxiliary probes on the measurements of the low frequency ground impedance with the fall-of-potential method are described and the testing techniques to minimize the measuring errors are proposed. The fall-of-potential method is theoretically based on the potential and current measuring principle and the measuring error is primarily caused by the position and angle of auxiliary probes. In order to analyze the characteristics of ground impedance due to the location of the potential probe, ground impedances were measured in case that the distance of current probe was fixed at 50[m] and the distance of potential probe was located from 10[m] to 50[m]. Also, the potential probe was located at 30[°], 45[°], 60[°], 90[°], and 180[°]. The results could be help to determine the location of potential probe when the ground impedance was measured at grounding system.
      번역하기

      In this paper, the effects of the position and the angle of the auxiliary probes on the measurements of the low frequency ground impedance with the fall-of-potential method are described and the testing techniques to minimize the measuring errors are...

      In this paper, the effects of the position and the angle of the auxiliary probes on the measurements of the low frequency ground impedance with the fall-of-potential method are described and the testing techniques to minimize the measuring errors are proposed. The fall-of-potential method is theoretically based on the potential and current measuring principle and the measuring error is primarily caused by the position and angle of auxiliary probes. In order to analyze the characteristics of ground impedance due to the location of the potential probe, ground impedances were measured in case that the distance of current probe was fixed at 50[m] and the distance of potential probe was located from 10[m] to 50[m]. Also, the potential probe was located at 30[°], 45[°], 60[°], 90[°], and 180[°]. The results could be help to determine the location of potential probe when the ground impedance was measured at grounding system.

      더보기

      목차 (Table of Contents)

      • Abstract
      • 1. 서론
      • 2. 측정방법
      • 3. 결과 및 고찰
      • 4. 결론
      • Abstract
      • 1. 서론
      • 2. 측정방법
      • 3. 결과 및 고찰
      • 4. 결론
      • 참고문헌
      더보기

      동일학술지(권/호) 다른 논문

      동일학술지 더보기

      더보기

      분석정보

      View

      상세정보조회

      0

      Usage

      원문다운로드

      0

      대출신청

      0

      복사신청

      0

      EDDS신청

      0

      동일 주제 내 활용도 TOP

      더보기

      주제

      연도별 연구동향

      연도별 활용동향

      연관논문

      연구자 네트워크맵

      공동연구자 (7)

      유사연구자 (20) 활용도상위20명

      이 자료와 함께 이용한 RISS 자료

      나만을 위한 추천자료

      해외이동버튼