Recently, underground transmission system is growing continuously according to the electric power demand increase in the downtown area. Even if domestic cable makers are manufacturing 154kV oil filled cable and joint, the design technology of cable-jo...
Recently, underground transmission system is growing continuously according to the electric power demand increase in the downtown area. Even if domestic cable makers are manufacturing 154kV oil filled cable and joint, the design technology of cable-joint has not been fully self-reliance. This study is aimed at the detail heat transfer analysis of 154kV cable-joint. So, that is cut into the five sections in order to analyze a conjugate natural convection in two dimensional $r-{\theta}$ coordinate. The streamline and temperature distributions are obtained for each sections. Also the changes of those are analyzed with respect to the variation of transmission currents and cable-joint surface heat transfer coefficients. The same analyses are also shown in view point of the maximum temperature of conductor and local equivalent conductivity.