    전자교환시스템 냉각을 위한 히트파이프 적용 연구 = A study on the application of heat pipe to the cooling of ATM switching system

    한글로보기

    https://www.riss.kr/link?id=A106774120

    • 0

      상세조회
    • 0

      다운로드
    서지정보 열기
    • 내보내기
    • 내책장담기
    • 공유하기
      • URL 복사
    • 오류접수
    인용문이 복사되었습니다.

    부가정보

    다국어 초록 (Multilingual Abstract) kakao i 다국어 번역

    In the present study, the cooling package using the heat pipe has been developed to improve the thermal performance in the point of cooling characteristics of the electronic chip placed to the subrack being readily assembled and disassembled in ATM switching system. As the preliminary experiments, the cooling performances between a conventional way using a cooling fin and a proposed method applying the heat pipe are compared and analyzed. The cooling performance at a simulated electronic component packaging a heat pipe module is approximately achieved up to $5.0W/cm^2$ heat flux and the allowable temperature at the heated chip is sustained in the range within $70^{\circ}C$. From the results, it is confirmed that temperature oscillations are also settled by inserted wick in the evaporator section. From the user's viewpoint, the method to assemble and disassemble the heat pipe easily has been devised.
    번역하기

    In the present study, the cooling package using the heat pipe has been developed to improve the thermal performance in the point of cooling characteristics of the electronic chip placed to the subrack being readily assembled and disassembled in ATM sw...

    In the present study, the cooling package using the heat pipe has been developed to improve the thermal performance in the point of cooling characteristics of the electronic chip placed to the subrack being readily assembled and disassembled in ATM switching system. As the preliminary experiments, the cooling performances between a conventional way using a cooling fin and a proposed method applying the heat pipe are compared and analyzed. The cooling performance at a simulated electronic component packaging a heat pipe module is approximately achieved up to $5.0W/cm^2$ heat flux and the allowable temperature at the heated chip is sustained in the range within $70^{\circ}C$. From the results, it is confirmed that temperature oscillations are also settled by inserted wick in the evaporator section. From the user's viewpoint, the method to assemble and disassemble the heat pipe easily has been devised.