      슬래브축열의 최적제어방책에 관한 연구 -평가함수의 선택이 결과에 미치는 영향- = A Study on the Optimal Control Strategy of Air-Conditioning System with Slab Thermal Storage-Results Influenced by the Choice of a Criterion Function-

      한글로보기

      https://www.riss.kr/link?id=A104423093

      • 0

        상세조회
      • 0

        다운로드
      서지정보 열기
      • 내보내기
      • 내책장담기
      • 공유하기
      • 오류접수

      부가정보

      다국어 초록 (Multilingual Abstract)

      An optimal control of an air-conditioning system with slab thermal storage is investigated by making use of the Maximum Principle. An optimal heat input to a plenum chamber and an air-conditioned room is determined by minimizing a criterion function which is given as integral sum of two terms. The first term is the square of the deviation in the room air temperature from the set-point value, and the second is the absolute value of the heat input. The result indicates that it tries to keep a room air temperature in set-point value by heating as much as possible at the time of a setup of a room air temperature or just before that, in order to avoid a heat loss arising at the time of the non-air conditioning. The result is compared with that of the case when the square of the heat input is used as a criterion.
      번역하기

      An optimal control of an air-conditioning system with slab thermal storage is investigated by making use of the Maximum Principle. An optimal heat input to a plenum chamber and an air-conditioned room is determined by minimizing a criterion function w...

      An optimal control of an air-conditioning system with slab thermal storage is investigated by making use of the Maximum Principle. An optimal heat input to a plenum chamber and an air-conditioned room is determined by minimizing a criterion function which is given as integral sum of two terms. The first term is the square of the deviation in the room air temperature from the set-point value, and the second is the absolute value of the heat input. The result indicates that it tries to keep a room air temperature in set-point value by heating as much as possible at the time of a setup of a room air temperature or just before that, in order to avoid a heat loss arising at the time of the non-air conditioning. The result is compared with that of the case when the square of the heat input is used as a criterion.

      더보기

      참고문헌 (Reference)

      1 "The mathematical theory of optimal processes" Gordon and Breach Science Publishers. me 4 : 1986

      2 "Simulation study on the performance of a fabric heat storage system" (544) : 31-38, 2001

      3 "Performance evaluation of floor thermal storage system" 106 (106): 311-316, 2000

      4 "Fundamental study into optimized control for air-conditioning system with floor thermal storage based on optimal control theory" (520) : 33-39, 1999

      5 "Fundamental study into optimized control for air-conditioning system with floor thermal storage" University of Kyoto 2004

      6 "An Experimental study on thermal storage performance of an air conditioning system with slab thermal storage" 17 (17): 427-435, 2005

      7 "A study on the optimal control strategy of air-conditioning system with slab thermal storage, The difference by the presence of radiant heat as a criterion factor" 18 (18): 287-296, 2006

      8 "A study on the indoor environment characteristics of air conditioning system with thermal storage capacity in slab-In the case of winter heating only" 1017-1022, 2003

      1 "The mathematical theory of optimal processes" Gordon and Breach Science Publishers. me 4 : 1986

      2 "Simulation study on the performance of a fabric heat storage system" (544) : 31-38, 2001

      3 "Performance evaluation of floor thermal storage system" 106 (106): 311-316, 2000

      4 "Fundamental study into optimized control for air-conditioning system with floor thermal storage based on optimal control theory" (520) : 33-39, 1999

      5 "Fundamental study into optimized control for air-conditioning system with floor thermal storage" University of Kyoto 2004

      6 "An Experimental study on thermal storage performance of an air conditioning system with slab thermal storage" 17 (17): 427-435, 2005

      7 "A study on the optimal control strategy of air-conditioning system with slab thermal storage, The difference by the presence of radiant heat as a criterion factor" 18 (18): 287-296, 2006

      8 "A study on the indoor environment characteristics of air conditioning system with thermal storage capacity in slab-In the case of winter heating only" 1017-1022, 2003