      전자현미경을 이용한 건물내 비고형 표면자재의 석면 오염 및 기중 석면농도 특성조사 = Characterization of Asbestos Content in Friable Sprayed - on Surface Material and Airborne Asbestos Concentrations in Buildings by TEM

      한글로보기

      https://www.riss.kr/link?id=A3356644

      • 0

        상세조회
      • 0

        다운로드
      서지정보 열기
      • 내보내기
      • 내책장담기
      • 공유하기
      • 오류접수

      부가정보

      다국어 초록 (Multilingual Abstract)

      Fourteen(14) large commercial buildings located in Seoul with friable sprayed-on surface insulation material on ceiling were investigated for fiber types in bulk material and for airborne fiber concentrations in buildings by transmission electron microscopy (TEM) in order to compare the results with those by polarized light microscopy (PLM) and phase contrast microscopy (PCM). The results were as follows:
      1. Chrysotile asbestos was found in one bulk sample out of total 14 bulk samples collected. Glass fiber and mineral wool were the two major constituents of the bulk samples.
      2. The Na-Mg-Si-Ca-Fe-Al ratios of the EDX spectra which were normalized with the Si peak were 0-1.0-10-8.3-4.0-4.0 in mineral wool and 0-5-10-21-0-0 in chrysotile asbestos, respectively.
      3. Airborne fiber concentrations were log-normalcy distributed and the geometric mean (geometric standard deviation) fiber concentrations by TEM in the underground parking lots and inside buildings were 0.0048 f/cc(1.93) and 0.0040 f/cc(2.27), respectively with no statistical difference. In the outdoor ambient air, statistically significantly lower concentration of 0.0018 f/cc(2.04) was measured.
      4. The TEM/PCM ratios of airborne fiber concentrations ranged 0.5 - 2.0 for 80 % of airborne samples analyzed, end the regression equation between TEM and PCM was PCM=-0.2724 +1.1355(TEM) with the coefficient of determination R²=0.52.
      The results of this study confirmed that the sprayed-on surface insulation material found in some commercial buildings may possibly be contaminated with asbestos fiber. Since statistically significant relationship of fiber concentrations measured by PCM and TEM inside buildings and ambient air was found, previous results by PCM in ambient air could be used to estimate the ambient fiber concentrations in knowing the ratio of TEM/PCM.
      번역하기

      Fourteen(14) large commercial buildings located in Seoul with friable sprayed-on surface insulation material on ceiling were investigated for fiber types in bulk material and for airborne fiber concentrations in buildings by transmission electron micr...

      Fourteen(14) large commercial buildings located in Seoul with friable sprayed-on surface insulation material on ceiling were investigated for fiber types in bulk material and for airborne fiber concentrations in buildings by transmission electron microscopy (TEM) in order to compare the results with those by polarized light microscopy (PLM) and phase contrast microscopy (PCM). The results were as follows:
      1. Chrysotile asbestos was found in one bulk sample out of total 14 bulk samples collected. Glass fiber and mineral wool were the two major constituents of the bulk samples.
      2. The Na-Mg-Si-Ca-Fe-Al ratios of the EDX spectra which were normalized with the Si peak were 0-1.0-10-8.3-4.0-4.0 in mineral wool and 0-5-10-21-0-0 in chrysotile asbestos, respectively.
      3. Airborne fiber concentrations were log-normalcy distributed and the geometric mean (geometric standard deviation) fiber concentrations by TEM in the underground parking lots and inside buildings were 0.0048 f/cc(1.93) and 0.0040 f/cc(2.27), respectively with no statistical difference. In the outdoor ambient air, statistically significantly lower concentration of 0.0018 f/cc(2.04) was measured.
      4. The TEM/PCM ratios of airborne fiber concentrations ranged 0.5 - 2.0 for 80 % of airborne samples analyzed, end the regression equation between TEM and PCM was PCM=-0.2724 +1.1355(TEM) with the coefficient of determination R²=0.52.
      The results of this study confirmed that the sprayed-on surface insulation material found in some commercial buildings may possibly be contaminated with asbestos fiber. Since statistically significant relationship of fiber concentrations measured by PCM and TEM inside buildings and ambient air was found, previous results by PCM in ambient air could be used to estimate the ambient fiber concentrations in knowing the ratio of TEM/PCM.