    Thermal Properties of KIV Electric Wires Subjected to Compression Damage

    한글로보기

    https://www.riss.kr/link?id=A108328588

    • 0

      상세조회
    • 0

      다운로드
    서지정보 열기
    • 내보내기
    • 내책장담기
    • 공유하기
      • URL 복사
    • 오류접수
    인용문이 복사되었습니다.

    부가정보

    다국어 초록 (Multilingual Abstract) kakao i 다국어 번역

    This study investigated the thermal properties of a KIV insulated wire subjected to compression damage. In the wire breakage measurement experiment for the compressed insulated wire, 25, 50, 75, and 95% compression damage were applied to the cross-sectional area of the wire using a compression testing machine, and a quantitative value of the applied load was derived. The applied load for 95% damage was found to be 110 kgf. An additional experiment was performed on the thermal properties of the wire cut by compression damage. At a current of 30 A, the maximum temperature of a normal sample was 28 °C and that of a sample with 95% damage increased by 31.9 °C to 59.9 °C within the same test time. At 45 A, the maximum temperature of a normal sample was 55.7 °C and that of a sample with 95% damage increased by 37.3 °C to 93 °C. At 60 A, the maximum temperature of a normal sample was 90.8 °C and that of a sample with 95% damage sharply increased by 103 °C to 193.8 °C. Because the wires of home appliances and electric devices are frequently used when pressed in daily life, caution needs to be exercised by using protective frames to prevent the compression of electric wires, and in turn prevent the occurrence of electric fires.
    번역하기

    This study investigated the thermal properties of a KIV insulated wire subjected to compression damage. In the wire breakage measurement experiment for the compressed insulated wire, 25, 50, 75, and 95% compression damage were applied to the cross-sec...

    This study investigated the thermal properties of a KIV insulated wire subjected to compression damage. In the wire breakage measurement experiment for the compressed insulated wire, 25, 50, 75, and 95% compression damage were applied to the cross-sectional area of the wire using a compression testing machine, and a quantitative value of the applied load was derived. The applied load for 95% damage was found to be 110 kgf. An additional experiment was performed on the thermal properties of the wire cut by compression damage. At a current of 30 A, the maximum temperature of a normal sample was 28 °C and that of a sample with 95% damage increased by 31.9 °C to 59.9 °C within the same test time. At 45 A, the maximum temperature of a normal sample was 55.7 °C and that of a sample with 95% damage increased by 37.3 °C to 93 °C. At 60 A, the maximum temperature of a normal sample was 90.8 °C and that of a sample with 95% damage sharply increased by 103 °C to 193.8 °C. Because the wires of home appliances and electric devices are frequently used when pressed in daily life, caution needs to be exercised by using protective frames to prevent the compression of electric wires, and in turn prevent the occurrence of electric fires.

    더보기

    목차 (Table of Contents)

    • 1. Introduction
    • 2. Experimental Sample and Scope
    • 3. Experiment
    • 4. Experimental Results and Discussion
    • 5. Conclusion
    • 1. Introduction
    • 2. Experimental Sample and Scope
    • 3. Experiment
    • 4. Experimental Results and Discussion
    • 5. Conclusion
    • Conflicts of Interest
    • References