Fouling is "a major unsolved" area in heat transfer research. Currently, fouling researches are performed in every directions-fundamental aspects, modeling and cumulating experimental data. In this study, an attempt was made to extend the knowledge in...
Fouling is "a major unsolved" area in heat transfer research. Currently, fouling researches are performed in every directions-fundamental aspects, modeling and cumulating experimental data. In this study, an attempt was made to extend the knowledge in enhanced tube fouling. The Kern-Seaton fouling model which was originally proposed for smooth tube fouling was extended to repeated rib tubes. Key parameters-mass transfer coefficient and wall shear stress-were modeled for repeated rib tubes. Some critical points related with the enhanced tube fouling-uncertainties in the mass transfer rate, wall shear stress modeling, deformation of roughness shape during fouling-were discussed, and some quantitative evaluations were made.