In the standard cooling conditions specified in KS C 9306, tests were performed for the case of no water injection
and the case of water injection at 70mm and 90mm distance in order to investigate the effect of the water injection
location on the air ...
In the standard cooling conditions specified in KS C 9306, tests were performed for the case of no water injection
and the case of water injection at 70mm and 90mm distance in order to investigate the effect of the water injection
location on the air conditioner performance. The refrigerant inlet area, the middle area, and the refrigerant outlet
area of the condenser were considered as injection location. As a result of the experiment, the case of injecting
water at 70mm distance on the refrigerant outlet area showed 7.1% COP improvement effect compared to the case
of not spraying.