6.6 kV 케이블의 절연저항 측정을 위한 부하전류 및 온도 측정
박용규,조영식,이관우,엄기홍,박대희,Park, Yong-Kyu,Cho, Young-Seek,Lee, Kwan-Woo,Um, Kee-Hong,Park, Dae-Hee 한국전기전자재료학회 2015 전기전자재료학회논문지 Vol.28 No.1
The cable degradation process is largely divided into three steps; Step 1 : Thermal degradation, Step 2 : Weibull degradation, Step 3 : Partial discharge. it is progress in step order. This article aims to explain the process of cable degradation using the method of insulation resistance and accordingly to compose and manufacture a system of measuring the life of electrical cable. Before measuring the insulation resistance, a system of measuring the temperature and current of cables was made, and the established system was installed for test on the site of a power plant to collect the measured data. The current sensor was used TFC30P80A-CL420, and temperature sensor was used the DK-1270 PT100 sensor as RTD sensor. When measured the temperature and the load current at the same position, was confirmed that in case of the load current value was high, also temperature value high. Therefore, the correlation between load currents and temperature was verified, and the analysis of diagnostic data was evaluated, which could be utilized in identifying the fault condition of cable systems.
전력케이블의 열화측정을 위한 부하전류 및 온도측정 시스템
박용규(Yong-Kyu Park),조영식(Young-Seek Cho),이관우(Kwan-Woo Lee),엄기홍(Kee-Hong Um),박대희(Dae-Hee Park) 한국조명·전기설비학회 2015 조명·전기설비학회논문지 Vol.29 No.2
Recently, there has been a surge in interest in equipment diagnosis and monitoring technology from the perspective of providing quality electricity in terms of reliability and safety. In order to meet the electrical demands of consumers, reliability of power supply needs to be maintained. For this purpose, a monitoring system for power cable is very important. Since real?time measuring equipment has many advantages, it is highly applicable. By measuring the load current and the surface temperature of power cables, we have monitored and identified the deterioration phenomena of power cables in operation. Since direct measurement of the cable conductor temperature is not easy, we have measured the surface temperature instead, and converted that temperature to obtain the conductor temperature of the cables. In addition, we have designed a system to detect the deterioration processes of the power cables in operation.