진창환(Chang-Hwan Jin),박대원(Dae-Won Park),서재석(Jae-Seok Seo),길경석(Gyung-Suk Kil),길형준(Hyeong-Jun Gil) 한국철도학회 2011 한국철도학회 학술발표대회논문집 Vol.2011 No.10
In measurement of risk voltages; the step and touch voltage the distance between the current electrode and the ground electrode recedes up to several hundred meters as the scale of grounding system increases. This paper dealt with the measurement method of risk voltage in a restricted space. The risk voltage was analyzed depending on the distance and the direction of the current electrode from the ground electrode in a 10 [m] * 10 [m] mesh grounding system. The average value of risk voltages measured at a point 20 [m] away from the current electrode was deviated below 5 [%] from that measured at 100 [m] point. Consequently the evaluation of risk voltage of a large-scale grounding system buried in a spatially restricted place is available if the current electrode is installed in symmetry to the ground electrode.