이동일(LEE D.I),신구용(Shin K.Y),임재섭(Lim J.S),이형권(Lee H.K) 대한전기학회 2010 대한전기학회 학술대회 논문집 Vol.2010 No.7
This paper has investigated and analyzed application status of live-line works to overhead transmission lines in foreign power utilities. The results of this paper will be useful data for applying live-line works to KEPCO 765 ㎸ Transmission lines.
Environmental Impact on the KEPCO 765-kV Double Circuit Transmission Line
이동일,신구용,김정부,Lee, D.I,Sin, K.Y,Kim, J.B The Korean Institute of Electrical Engineers 1999 전기학회논문지C Vol.48 No.2
The environmental impact of the KEPCO 765-kV transmission line was studied using a full scale test line in order to develop the design technology. Therefore this paper describes an environmental design summary of the audible noise, hum noise, wind noise, radio interference, TV interference and electric field measurement from the KEPRI 765-kV double circuit transmission test line with a bundle of $6-480mm^2$ conductors per phase. The analysis of the test results shows that 6-Rail and 6-Cardinal conductors bundle satisfy the audible noise criterion & TV interference under the stable rainy weather condition and the radio interference level under the fair weather. And the other items are also agreed with the design level criterion for KEPCO 765-kV transmission line.