Comparison of 2- and 3-level Active Filters with Enhanced Bridge-Leg Loss Distribution
Thiago B. Soeiro,Mario Schweizer,Jorgen Linner,Per Ranstad,Johann W. Kolar 전력전자학회 2011 ICPE(ISPE)논문집 Vol.2011 No.5
In this paper an efficiency comparison between 3-phase shunt active filters derived from the 2-level VSC, the 3-level NPC, Active NPC (A-NPC) and the T-type VSC is presented. In order to address the loss distribution issue of the 3-level topologies, while keeping the efficiency of the system high, a space vector modulation scheme incorporating a special clamping of the phase is proposed. It is shown that 3-level active filters can have their losses well distributed over the chip dies, leading to only a small difference in their operating temperatures. Additionally, a semiconductor area based comparison is used to further evaluate the studied active filter systems. Finally, experimental results obtained with a 12kVAr/48㎑ 3-level NPC based shunt active filter employing custom SiC power modules are presented in order to demonstrate the performance and feasibility of this solution.