http://chineseinput.net/에서 pinyin(병음)방식으로 중국어를 변환할 수 있습니다.
변환된 중국어를 복사하여 사용하시면 됩니다.
임효재(Hyojae Lim),손병후(Byonghu Sohn) 한국지열·수열에너지학회 2021 한국지열에너지학회논문집 Vol.17 No.2
This paper presents the heating performance analysis results of a heat pump system using a dual heat source. In this paper, a dual heat source refers to the ground-coupled heat exchanger using both a surface water heat exchanger (SWHE) and a vertical ground heat exchanger (VGHE). In order to evaluate the system performance, we installed a monitoring system to measure the temperature and power consumption of a heat pump and then collected operation data with 4 different load burdened ratios of the dual heat source heat exchanger. During the whole measurement period, the average heating capacity of a water-to-water heat pump unit was 37.3 kW. In addition, the compressor of the heat pump consumed 9.4 kW of power, while the circulating pump of the dual heat source heat exchanger used 6.7 kW of power. Therefore the average heating coefficient of performance (COP) for the heat pump unit was 4.0, while the entire system including the circulating pump was 2.7. Finally, the parallel use of SWHE and VGHE was beneficial to the system performance; however, further researches are needed to optimize the design data for various load ratios of the dual heat source heat exchanger.