http://chineseinput.net/에서 pinyin(병음)방식으로 중국어를 변환할 수 있습니다.
변환된 중국어를 복사하여 사용하시면 됩니다.
LABORATORY INVESTIGATION OF DIFFERENT EJECTOR GEOMETRIES FOR R-744 TRANSCRITICAL SYSTEMS
ARMIN HAFNER 대한설비공학회 2011 International Journal Of Air-Conditioning and Refr Vol.19 No.3
This work describes measurement results of ejectors manufactured and experimentally investigated at SINTEF Energy Research/NTNU. The ejectors are experimentally investigated in an oil free R-744 test facility in order to focus on the ejector properties and behavior. Five different ejectors were experimentally investigated at equal boundary conditions. The results are promising with pressure lifts close to 9 bars at low mass entrainment ratios of 0.22 and suction pressure ratios of 1.24. At an higher mass entrainment ratio of 0.56 and suction pressure ratio of 1.14 a pressure lift of 6.5 bar was achieved with the smallest mixing section. Best performances were measured with the smallest mixing section diameter (3 mm) and a short nozzle with an ID of 0.9 mm. The results are very promising and show a very good Coefficient of Performance improvement potential for R-744 transcritical process deploying an ejector, as the pressure ratio for a compressor could be reduced by close to 10 bars.