http://chineseinput.net/에서 pinyin(병음)방식으로 중국어를 변환할 수 있습니다.
변환된 중국어를 복사하여 사용하시면 됩니다.
K. W. Yong,P. B. Ganesan,E. Hamidi,S. N. Kazi,S. Ramesh 대한설비공학회 2020 International Journal Of Air-Conditioning and Refr Vol.28 No.4
The present study investigates the water retention behavior in two different types of porous media, i.e., porous metal — a type of metallic foam and ideal geometry. The present study uses computational fluid dynamics (CFD) to model a decreasing water level in a reservoir consisting of a stationary porous medium beneath the water surface at initial stage. It mimics the setup of dynamics dip-testing which measures the amount of retained water for different types of fins-tubes heat exchangers. The study varies parameters like static contact angle (θ s)and drainage velocity (U). The literature review summarizes the unique water retention behaviors for different types of heat exchangers and the findings of the present study. Furthermore, the present study proposed new parameters for evaluating the structural variations in porous metal that explains the water saturation distribution in detail. The evaluation method could provide an insightful idea for performing the quality control check on metallic foam.