응축수 맺힘조건에서 슬릿형상을 갖는 핀-튜브 열교환기의 공기측 열전달 특성
김용배(Yongbae Kim),윤린(Rin Yun),김용찬(Yongchan Kim),문동수(Dongsoo Moon),홍기수(Kisu Hong),진심원(Simwon Chin) 대한기계학회 2005 대한기계학회 춘추학술대회 Vol.2005 No.5
An experimental study was performed in compact finned tube heat exchangers under wetting conditions. Five finned tube heat exchangers having slit fin were tested. The number of tube rows was 1, 2, and 3, and the tube diameters were 7.35 and 9.95 ㎜. The air-side heat transfer coefficients were calculated by the log-mean-enthalpy-difference method, which were presented in terms of j-factor. The effects of tube diameter, the number of tube rows and inlet humilities on air-side heat transfer characteristics were investigated. The effects of wetting surface on the j-factor become more significant with increasing of the Reynolds number and with decreasing of the number of tube rows.