저심도 대구경 지중열교환기의 설치조건에 따른 성능 연구
유규상(Gyu Sang Yoo),박일문(Il Mun Park),최재호(Jae Ho Choi),신현준(Hyun-Joon Shin) 대한설비공학회 2009 대한설비공학회 학술발표대회논문집 Vol.2009 No.-
A ground-loop heat exchanger for the ground source heat pump system is the core equipment determining the thermal performance and initial cost of the system. The size and performance of the heat exchanger is highly dependent on the ground thermal properties - the ground effective thermal conductivity, the borehole thermal resistance and the undisturbed ground temperature. Nowadays, precast concrete piles using steel reinforced precast concrete piles - energy piles - are used to reduce the installing cost of the ground-loop heat exchanger. We were carried out some tests to investigate the effects of some parameters such as borehole length, grouting materials and U-tube configuration of the energy piles. 4 concrete piles, each measuring 250㎜~400㎜ in diameter and approx. 10m in length, and rigged with single spiral and 3 U-tube loop of 16㎜ X 2.3㎜ PB piping. The thermal response tests were conducted using a testing device for 4-different ground-loop heat exchangers. During the heating period, the energy piles absorb the heat of 0.89㎾ to 1.37㎾.