난방 부하에 따른 열교환기 설계 변경이 전열량에 미치는 영향
곽유섭(Yu Sub Kwak),정지환(Ji Hwan Jeong) 대한설비공학회 2018 대한설비공학회 학술발표대회논문집 Vol.2018 No.11
Commonly, the heat pump has a short operating time under rated conditions and a long operating time under partial load conditions. However, most heat exchangers are designed to focus on rated conditions rather than partial load conditions. Therefore, in this study, the difference of heat transfer performance was examined by different design of heat exchanger according to partial load conditions. It is important to determine the number of paths because the influence of the number of paths is greatest among design parameters of the heat exchanger. The methodology used is that the optimum path number of the heat exchanger is calculated when the refrigerant heat resistance and the air heat resistance are the same. When the design of the heat exchanger was changed, the maximum and minimum difference in total heat transfer performance was maximum 5.9% and minimum 2.0%.