A Numerical study was carried out for a propane gas pool fire in the fire test room of 2.5 m×2.0 m×2.5 m for testing a inert gas water mist system, to investigate a possible under-ventilation in the fire test room. For the fire sizes of 60 Kw and 12...
A Numerical study was carried out for a propane gas pool fire in the fire test room of 2.5 m×2.0 m×2.5 m for testing a inert gas water mist system, to investigate a possible under-ventilation in the fire test room. For the fire sizes of 60 Kw and 120 Kw, changes in the temperature and CO concentration with and without a window were investigated. It was confirmed that the influence of the window on the distributions of temperature and CO concentration was small in the two fire sizes, and hence the under-ventilation was not occurred in the room.