공조 시스템 내의 MFHE에서 이루어지는 2상 냉매 분배에 대한 수치해석
박재현(Jae Hyun Park),천영민(Yeong Min Cheon),박장한(Jang Han Park),박일석(Il Seouk Park) 대한기계학회 2015 대한기계학회 춘추학술대회 Vol.2015 No.11
To increase the heat exchange efficiency at MFHE(Multi Flow Heat Exchanger) in the air-conditioning system, Numerical analysis be studied for two-phase refrigerant uniformly distributed to each tubes. The domain of analysis include evaporator inlet header, outlet header and tube between two headers. Standard k-eqsilon model is used to analyze turbulent flow in the header and VOF(Volume Of Fluid) model is used to analyze two-phase flow that gas and liquid-phase present in the MFHE. The flow regime of the header inlet is stratified flow. Inlet direction, tube length and tube protrusion depth were investigated as a main factor to affect two-phase flow refrigerant distribution. Inlet direction change model induce maldistribution in tube close to inlet. Tube length change model also increase flow maldistribution. Protrusion depth model more uniformly distribute two-phase flow refrigerant better than other factors.