고체절연차단기(Solid Insulated Switchgear)용 PD 센서 선정에 관한 연구
이도훈(Do-Hoon Lee),강원종(Won-Jon Kang),마지훈(Ji-Hoon Ma),박석원(Seok-Weon Park),이종호(Jhong-Ho Lee) 대한전기학회 2010 대한전기학회 학술대회 논문집 Vol.2010 No.7
Defects in the epoxy insulation switchgear can result in failure. Therefore it is important to detect defects, such as void, in time and to determine their risk for a possible breakdown. For high voltage apparatus, the partial discharge (PD) detection technology has proven to be a useful method. This paper describes the application of a PD detection method for the Solid Insulated switchgear(SIS) and its practical application. Experimental studies show that the PD detection of the MV switchgear defects is possible. The practical experiences related to this study provide further insight for applying the PD monitoring technique to the solid insulated switchgears.
25.8㎸급 친환경 고체절연차단기(Solid Insulated Switchgear)에 대한 기계적 신뢰성(수명) 평가
이도훈(Do-Hoon Lee),이석원(Seog-Won Lee),박석원(Seok-Weon Park),김영근(Young-Geun Kim),이종호(Jhong-Ho Lee) 대한전기학회 2010 전기학회논문지 P Vol.59 No.2
In this paper, mechanical reliability(Life-time) estimation method for 25.8kV SIS(Solid Insulated Switchgear) has been studied. Recently enacted KEPCO's standard includes clause that have to submit a warrantable reliability data for life-time(over B10 25 years) of an epoxy-solid insulating material. Accordingly, this research was carried out on the ALT(Accelerated Life Test) and Life-Estimation method for SIS's insulating material. Mechanical life-time estimation for SIS's insulating material is to verify reliability for tensile creep & fatigue stress, which is the major mechanical stress of SIS. This study proved that SIS's reliability for mechanical stress and established that confidence for estimation results in further verification test.
싸이클로알리파틱과 비스페놀F 에폭시 수지의 혼합 비율에 따른 내트래킹 특성
정해은(Hae-Eun Jung),강한영(Han-Young Kang),우두영(Doo-Young Woo),유한상(Han-Sang Yu),박석원(Seok-Weon Park),이종호(Jhong-Ho Lee) 대한전기학회 2010 대한전기학회 학술대회 논문집 Vol.2010 No.7
비스페놀 계열의 에폭시와 싸이클로알리파틱 에폭시를 가각 mol-wt%비(20:80, 50:50, 80:20)로 혼합하고 실란실리카, 각형용융실리카, 구형용융실리카, ATH를 충진하여 이종 에폭시 수지의 혼합비율 및 충진재에 따른 내트래킹 특성을 비교하였다. 전체 혼합물 중, 에폭시는 36%, 실리카 등의 충진재는 64%이다. 실험결과 싸이클로알리파틱의 혼합 비율이 높을수록 내트래킹 특성이 향상되었으나 그 정도가 크지는 않았다. 또한, 실란처리된 실리카를 사용하고, ATH 함량이 높을수록 내트래킹 특성이 향상되었다. 싸이클로알리파틱 수지의 혼합을 통해서는 IEC60587 4.5㎸ 등급을 만족하지는 못하였다.