최영휴(Young-Hyu Choi),김수태(Soo-Tae Kim),설상석(Sang-Seok Seol),문성춘(Sung-Choon Moon) 한국기계가공학회 2020 한국기계가공학회지 Vol.19 No.4
In this study, a response spectrum analysis of an electric distributing board (EDB) was conducted to investigate seismic integrity in the design stage. For the seismic analysis, the required response spectra of a safe shutdown earthquake with 2% damping (RRS/SSE-2%) specified in GR-63-CORE Zone 4 was used as the ground spectral acceleration input. A finite element method modal analysis of the EDB was also performed to examine the occurrence of resonance within the frequency range of the earthquake response spectrum. Furthermore, static stress caused by deadweight was analyzed. The resultant total maximum stress of the EDB structure was calculated by adding the maximum stresses from both seismic and static loads using the square root of the sum of the squares (SRSS) method. Finally, the structural safety of the EDB was investigated by comparing the resultant total maximum stress with the allowable stress.