http://chineseinput.net/에서 pinyin(병음)방식으로 중국어를 변환할 수 있습니다.
변환된 중국어를 복사하여 사용하시면 됩니다.
하이브리드 로켓의 저주파불안정성에 미치는 당량비 영향 직접수치해석
최효상,이창진,강상훈 한국추진공학회 2019 한국추진공학회지 Vol.23 No.2
To understand the low frequency instability(LFI) characteristics in hybrid rockets combustion, effects of equivalence ratio variations on the phase shift between pressure and heat release oscillations were investigated by using the direct numerical simulation. The change in the equivalence ratio of the main chamber was simulated by the temperature and composition variation of the combustion gas introduced into the post-combustion chamber. In the results, additional combustion appeared along with vortex generation at the backward step, and combustion pressure and heat release oscillations were observed as the vortex moved. In addition, the results confirmed that the phase difference between the pressure and heat release oscillation shifts because of the changes in the propagation velocity of pressure wave as the temperature of combustion gas changes. 하이브리드로켓의 저주파수 연소불안정(LFI) 특성을 이해하기 위해, 주연소실의 연소 당량비 변화가 500 Hz대역의 압력 및 열방출 진동의 위상변화에 미치는 영향에 대해 직접수치해석을 수행하였다. 주연소실의 당량비 변화는 후연소실로 유입되는 연소가스의 온도 및 조성 변화로 모사하였다. 수치해석 결과, 후향 계단 하류에 와류 생성과 함께 추가적인 연소가 나타나며, 와류가 이동함에 따라 연소 압력 및 반응률의 진동이 관찰되었다. 또한, 유입유동의 온도가 변화하면 압력파의 전파속도도 함께 변화하므로 압력 및 반응률 진동 사이의 위상차가 천이하게 됨을 확인하였다.
최효상,현옥배,김혜림,황시돌 한국전기전자재료학회 2000 전기전자재료학회논문지 Vol.13 No.12
We investigated resistive superconducting fault current limites (SFCLs) fabricated using YBCO thin films on 2-inch diameter sapphire substrates. Nearly identical SFCL units were prepared and tested. The units were connected in series and parallel to increase the current and voltage ratings. A serial connection of the units showed significantly unbalanced power dissipation between the units. This imbalance was removed by introducing a shunt resistor to the firstly quenched unit. Parallel connection of the units increased the current rating. An SFCL module of 4 units in parallel, each of which has minimum quench current rating. An SFCL module of 4 units in parallel, each of which has minimum quench current 25 A$\_$peak/, was produced and successfully tested at a 220 V$\_$rms/circuit. From the resistance increase, we estimated that the film temperature increased to 200 K in 5 msec, and 300 K in 120 msec. Successive quenches revealed that this system is stable without degradation in the current limiting capability under such thermal shocks as quenches at 220 V$\_$rms/.
1선 지락사고에 대한 배전급 저항형 초전도 한류기의 전류제한특성
최효상,황시돌,현옥배 한국전기전자재료학회 2001 전기전자재료학회논문지 Vol.14 No.6
We simulated the current limiting characteristics of a resistive superconducting fault current limiter (SFCL) for a single line-to-ground fault in the 22.9 kV system. The transient current during the fault increased to 6.33 kA, 5.80 kA and 3.71 kA without SFCL at the fault angles 0$^{\circ}$, 45$^{\circ}$ and 90$^{\circ}$, respectively, a resistive SFCL limited effectively the fault current to 2.27 kA in a half cycle without any DC components. The maximum quench resistance of an SFCL, 16Ω was suggested to be appropriate to limit the fault current in the 22.9 kV distribution system, considering the operating cooperation of a protective relay and the current limiting performance of an SFCL.
최효상,현옥배,김혜림,황시돌,Choi, Hyo-Sang,Hyun, Ok-Bae,Kim, Hye-Rim,Hwang, Si-Dole 한국초전도저온공학회 2000 한국초전도저온공학회논문지 Vol.2 No.2
We fabricated a resistive superconducting fault current limiter (SFCL) of meander type based on a YBCO film. In order to disperse the heat generated at hot spots in the YBCO film the film was coated with a gold shunt layer. When diodes were inserted in the parallel circuit to restrict the temperature increase in the SFCL element by reducing power supply cycles, the voltage could be increased to $\sqrt{2}$ times with the same quench resistance at a half and full cycles.
최효상,이나영,이상일,Choi, Hyo-Sang,Lee, Na-Young,Lee, Sang-Il 한국전기전자재료학회 2005 전기전자재료학회논문지 Vol.18 No.9
We investigated the unbalanced characteristics of the superconducting fault current limiters (SFCLs) based on YBCO thin films with a single line-to-ground fault. When a single line-to-ground fault occurred, the short circuit current of a fault phase increased about 6 times of transport currents after the fault onset but was effectively limited to the designed current level within 2 ms by the resistance development of the SFCL. The fault currents of the sound phases almost did not change because of their direct grounding system. The unbalanced rates of a fault phase were distributed from 6.4 to 1.4. It was found that the unbalanced rates of currents were noticeably improved within one cycle after the fault onset. We calculated the zero phase currents for a single line-to-ground fault using the balanced component analysis. The positive sequence resistance was reduced remarkably right after the fault onset but eventually approached the balanced positive resistance component prior to the system fault. This means that the system reaches almost the three-phase balanced state in about 60 ms after the fault onset at the three-phase system.
YBa<sub>2</sub>Cu<sub>3</sub>O<sub>7</sub> 박막을 이용한 하이브리드형 초전도 사고전류제한기의 특성
최효상,조용선,Choi, Hyo-Sang,Cho, Yong-Sun 한국전기전자재료학회 2006 전기전자재료학회논문지 Vol.19 No.4
We present investigations of a hybrid type superconducting fault current limiter (SFCL), which consists of transformers and resistive superconducting elements. The secondary windings of the transformer were separated into several electrically isolated circuits and linked inductively with each other by mutual flux, each of which has a superconducting current limiting element of $YBa_2Cu_3O_7$ (YBCO) stripes as a current limiting element. Simple connection in series of the SFCL elements tends to produce ill-timed quenching because of power dissipation unbalance between SFCL elements. Both electrical isolation and mutual flux linkage of the elements provides a solution to power dissipation unbalance, inducing simultaneous quench and current redistribution of the YBCO films. This design enables to increase the voltage rating of SFCL with given YBCO stripes.
최효상,Choi, Hyo-Sang 한국전기전자재료학회 2004 전기전자재료학회논문지 Vol.17 No.6
We present the basic properties of a superconductive fuse (SF) based on YBCO/Au films. The SF consists of YBCO stripes covered with Au layers for current shunt. The fault current was limited to a designed value in less than 0.4 msec by resistance development in YBCO/Au upon quenching. This enabled the SF to transfer small fault power and the suppressed current was sustained for more than 0.5 msec while Au layer melting and arcing. The arcing time was less than 2.5 msec, that is short enough to do self-interruption. Under the source voltage of 100 $V_{rms}$, the longer the duration time of fault current was, the shorter its discharge time was. The duration time of fault current and its discharge time were reduced by increased voltages in the range of 200 - 300 $V_{rms}$. We thought that this was because the quench propagation was limited by local melting generated with higher voltage.age.